ErP regulatory datasheets

ErP regulatory datasheets for products EYOTA 300, 450 et 600 (Eco-design directive no. 1254/2014/EU)

ParameterValue
VMI® model designationEYOTA 300 CO2 LH et EYOTA 300 RH
Supplier nameVentilairsec
Energy classA+
Average climate – SEC – Specific energy consumption (kWh/(m2 a))-42.38
Cold climate – SEC – Specific energy consumption (kWh/(m2 a))-16.78
Warm climate – SEC – Specific energy consumption (kWh/(m2 a))-87.85
Flow typeDouble flow
Declared typologyRVU/BVU
Type of drive installed or intendedVariable speed
Type of heat recovery systemHeat recovery
Thermal efficiency of heat recovery (%)93
Maximum flow rate of RVU (m3/h)300
Electric power input at Qmax (W)166
LwA – Sound power level (dB(A))48.5
Reference flow rate (m3/s)0.05833
Reference pressure (Pa)50
SPI (kW/m3/h)0.36
Control factor CTRL (%)N/A
Control typologyLocal demand control
Max. internal and external leakage rate (%) of BVUs<5% internal / <5% external
Filter alarm informationSee manual
Regular filter replacement for unit performance and efficiencySee manual
Installation instructions for ventilation grillesSee manual
Preassembly/disassembly instructions (internet)See manual
Airflow sensitivity to pressure variations at + 20 PaN/A
Airflow sensitivity to pressure variations at - 20 PaN/A
Indoor/outdoor airtightness (m3/h)N/A
Annual electricity consumption (kWh/a)2.34
Average climate – AHS – Annual heating saving (kWh/(m2.a))47.56
Cold climate – AHS – Annual heating saving (kWh/(m2.a))93.03
Warm climate – AHS – Annual heating saving (kWh/(m2.a))21.50
ParameterValue
VMI® model designationEYOTA 450 CO2 LH et EYOTA 450 RH
Supplier nameVentilairsec
Energy classA+
Average climate - SEC - Specific energy consumption (kWh/(m2 a))-44,38
Cold climate - SEC - Specific energy consumption (kWh/(m2 a))-89,46
Warm climate - SEC - Specific energy consumption (in kWh/(m2 a))-19,01
Type of flowDF
Declared typologyRVU/BVU
Type of motorization installed or plannedVariable speed
Type of heat recovery systemRecovery unit
Thermal efficiency of heat recovery (in %)91
Maximum flow rate of RVU (in m3/h)450
Electrical power input at Qmax (in W)206
LwA - Sound power level (in dB(A))49,0
Reference flow rate (in m3/s)0,08750
Reference pressure (Pa)50
SPI (in kW/m3/h)0,17
CTRL control factor (in %)N/A
Typology of regulationLocal demand control
Max. internal and external leakage rate (%) of BVUs<5% internal / <5% external
Filter alarm informationSee manual
Regular replacement of filters for unit performance and efficiencySee manual
Installation instructions for ventilation grillesN/A
Pre-assembly/disassembly instructions (internet)See manual
Airflow sensitivity to pressure variations at + 20 PaN/A
Airflow sensitivity to pressure variations at - 20 PaN/A
Etanchéité à l'air intérieur/extérieur (m3/h)N/A
Consommation électrique annuelle KWh/an1,37
Climat moyen – EAC – Economie annuelle de chauffage (kWh/m2.an)47,14
Climat froid – EAC – Economie annuelle de chauffage (kWh/m2.an)92,22
Climat chaud – EAC – Economie annuelle de chauffage (kWh/m2.an)21,32
ParameterValue
VMI® model designationEYOTA 600 CO2 LH et EYOTA 600 RH
Supplier nameVentilairsec
Energy classA+
Average climate – SEC – Specific energy consumption (kWh/(m2 a))-43.31
Cold climate – SEC – Specific energy consumption (kWh/(m2 a))-87.99
Warm climate – SEC – Specific energy consumption (kWh/(m2 a))-18.16
Flow typeDouble flow
Declared typologyRVU/BVU
Type of drive installed or intendedVariable speed
Type of heat recovery systemHeat recovery
Thermal efficiency of heat recovery (%)89
Maximum flow rate of RVU (m3/h)600
Electric power input at Qmax (W)338
LwA – Sound power level (dB(A))56.0
Reference flow rate (m3/s)0.11669
Reference pressure (Pa)50
SPI (kW/m3/h)0.22
Control factor CTRL (%)N/A
Control typologyLocal demand control
Max. internal and external leakage rate (%) of BVUs<5% internal / <5% external
Filter alarm informationSee manual
Regular filter replacement for unit performance and efficiencySee manual
Installation instructions for ventilation grillesN/A
Preassembly/disassembly instructions (internet)See manual
Airflow sensitivity to pressure variations at + 20 PaN/A
Airflow sensitivity to pressure variations at - 20 PaN/A
Indoor/outdoor airtightness (m3/h)N/A
Annual electricity consumption (kWh/a)1.64
Average climate – AHS – Annual heating saving (kWh/(m2.a))46.73
Cold climate – AHS – Annual heating saving (kWh/(m2.a))91.41
Warm climate – AHS – Annual heating saving (kWh/(m2.a))21.13

Display the Energy Labels of VMI Eyota 300, 450 and 600